| Thermo Scientific NESLAB ThermoFlex Specifications |
| |
ThermoFlex 900
Recirculating Chiller
|
ThermoFlex 1400
Recirculating Chiller
|
ThermoFlex 2500
Recirculating Chiller
|
ThermoFlex 3500
Recirculating Chiller
|
ThermoFlex 5000
Recirculating Chiller
|
| |
|
|
|
 |
 |
| Setpoint Temperature Range |
+5°C to +40°C
(+41°F to +104°F) |
+5°C to +40°C
(+41°F to +104°F) |
+5°C to +40°C
(+41°F to +104°F) |
+5°C to +40°C
(+41°F to +104°F) |
+5°C to +40°C
(+41°F to +104°F) |
| Ambient Temperature Range |
+10°C to +40°C
(+50°F to +104°F) |
+10°C to +40°C
(+50°F to +104°F) |
+10°C to +40°C
(+50°F to +104°F) |
+10°C to +40°C
(+50°F to +104°F) |
+10°C to +40°C
(+50°F to +104°F) |
| Temperature Stability |
±0.1°C |
±0.1°C |
±0.1°C |
±0.1°C |
±0.1°C |
Setpoint Cooling Capacity
60 Hz at +20°C
50 Hz at +20°C |
900 W / 3074 BTU
750 W / 2561 BTU |
1400 W / 4781 BTU
1170 W / 3996 BTU |
2500 W / 8538 BTU
2200 W / 7513 BTU |
3500 W / 11953 BTU
3050 W / 10416 BTU |
5000 W / 17076 BTU
4400 W / 15027 BTU |
| Reservoir Volume |
7.2 liters (1.9 gallons) |
7.2 liters (1.9 gallons) |
7.2 liters (1.9 gallons) |
7.2 liters (1.9 gallons) |
7.2 liters (1.9 gallons) |
|
Physical Dimensions
(H x W x D)
|
69.4 x 36.1 x 62.5
(27.3 x 14.2 x 24.6) |
69.4 x 36.1 x 62.5
(27.3 x 14.2 x 24.6) |
73.7 x 43.7 x 67.3
(29.0 x 17.2 x 26.5) |
98.8 x 49.0 x 78.2
(38.9 x 19.3 x 30.8) |
98.8 x 49.0 x 78.2
(38.9 x 19.3 x 30.8) |
P1— Positive Displacement Pump
60 Hz
50 Hz |
2.1 gpm @ 60 psid
1.7 gpm @ 60 psid |
2.1 gpm @ 60 psid
1.7 gpm @ 60 psid |
2.1 gpm @ 60 psid
1.7 gpm @ 60 psid |
2.1 gpm @ 60 psid
1.7 gpm @ 60 psid |
n/a |
|
P2— Positive Displacement Pump
60 Hz
50 Hz
|
4.1 gpm @ 60 psid
3.3 gpm @ 60 psid |
4.1 gpm @ 60 psid
3.3 gpm @ 60 psid |
4.1 gpm @ 60 psid
3.3 gpm @ 60 psid |
4.1 gpm @ 60 psid
3.3 gpm @ 60 psid |
4.1 gpm @ 60 psid
3.3 gpm @ 60 psid |
P3— Centrifugal Pump
60 Hz
50 Hz |
—
— |
—
— |
—
—
|
10 gpm @ 32 psid
10 gpm @ 20 psid |
10 gpm @ 32 psid
10 gpm @ 20 psid |
P4— Centrifugal Pump
60 Hz
50 Hz |
—
— |
—
— |
—
— |
15 gpm @ 57 psid
15 gpm @ 34 psid
|
15 gpm @ 57 psid
15 gpm @ 34 psid |
Unit Weight*
(by pump type) |
P1: 57.2 kg (126 lb)
P2: 57.2 kg (126 lb) |
P1: 57.2 kg (126 lb)
P2: 57.2 kg (126 lb) |
P1: 80.3 kg (177 lb)
P2: 80.3 kg (177 lb) |
P1: 120 kg (264 lb)
P2: 120 kg (264 lb)
P3: 123 kg (270 lb)
P4: 138 kg (303 lb) |
P2: 120 kg (264 lb)
P3: 123 kg (270 lb)
P4: 138 kg (303 lb) |
Voltage Options
115V/60Hz & 100V/50 Hz
100V/60Hz
208-230V/60Hz &
200V/50Hz
200V/60Hz†
230V/50Hz
Global Voltage
50Hz/60Hz
|
Available
Available
Available
Available
Available
Available |
Available
Available
Available
Available
Available
Available |
—
—
Available
Available
Available
Available |
—
—
Available
Available
Available
Available** |
—
—
Available
Available
Available
Available** |
|
Standard Compliance
|
 |
Specifications obtained at sea level using water as the recirculating fluid, at a +20°C process setpoint, +25°C ambient condition, at nominal operating voltage.
Other fluids, fluid temperatures, ambient temperatures, altitude or operating voltages will affect performance.
*Unit weight is for air-cooled units. Subtract 14 kg (30 lb) for water-cooled units. †This selection requires the global voltage option. **Add 12 kg (27 lb) to unit weight. |